Menu
Your Cart

AE604

AE604
AE604
AE604
AE604
AE604
AE604
AE604
AE604
AE604

Description

VAE COMPACT, ALL-IN-ONE, 4 ZONES  EVACUATION SYSTEMS EN54-16 EN54-4 CERTIFIED

  • Model: AE604
  • Weight: 29.20Kg
  • EAN: 8032496466581
  • This product has a minimum quantity of 1
Compare this Product

With AE300 we were pioneers, with AE604 we are innovators. Wall mounted All-In-One voice alarm system compliant with EN54-16 testing and charge circuit compliant with EN54-4. 4 Zones System on redundant loudspeaker line and backup Amplifier. Main and backup amplifier in class D “Pure Path”™. 300W + 300W (600W Total) @ 100V on redundant loudspeaker line (A + B). The system does not require a line end resistor. The system ensures full power performance even with backup power. Processing circuit by DSP; balanced and isolated background music input, isolated and balanced background music microphone input with selectable 48Vdc phantom power supply and priority activation by contact; monitored input for remote emergency call stations; front panel fitted with monitor loudspeaker, monitored emergency PPT microphone, direct sending message keys, navigation keys, large display with LCD dot matrix. Line output; audio messages stored on uSD 16bit 48kHz: 8 general purpose messages with activation from dedicated input, contacts or incorporated scheduler, 8 monitored contacts for emergency announcement activation. 4pcs. 12Vdc batteries 18Ah not included.

Model AE604 
Main power source AC mains 220V - 50/60Hz
Backup power source 48V – built-in batteries (4x 12V 18A/h sealed lead acid)
Backup power unit life 36h stand-by + 0.5h full power
Maximum power consumption 700W
Constant voltage600W rms @ 1% THD on 100V loudspeaker line, all zones comvined
Frequency response100Hz – 18Khz @ -3dB
Signal to noise ratio>90dB
Redundant power amplifier Yes Zones and loudspeaker lines 4 zones, redundant louduspeaker lines (A+B) on each zone
Loudspeaker line monitoring 20 KhZ FFT impedance measurement +/-5% range. Detection of line cut, line short, line grounding. No end of line needed
User interfaceStatus leds + dot-matrix display, menu navigation keyboard, direct access status keys (alarm, warning, silencing)
Audio processing DSP based, 16bit-48Khz; 3-band equalizer, Compressor/expander on microphone inputs; Pre-gain and master volume controls; Chime
Audio inputs/outputs Background music; microphone input with phantom supply and enable contact input. Subwoofer line output
Front panel loudspeaker monitor Yes
Emergency Firemen microphones Frontpanel microphone with monitored capsule RJ14 input for WG-MTU01 desktop emergency call station
General input controls 8x dry contact inputs triggers for general announcement messages
General message scheduler Yes
Input controls from fire alarm devices 2x monitored input contacts against cable-cut and cable short. Alarm, warning
Output status reporting 3x 1A 230V relay contacts (alarm, fault, disablement)
Communication RS485, USB diagnostic port, Ethernet 10 BASE-T/100
Battery monitoring Internal resistance DC measurement
Certifications and compliancyEN54-16, EN54-4, BS-EN5839-8, 60849
Access restriction Key-locked front door, password protected access to system menu
Chassiss and dimensions Main Unit: W:470mm - H: 550mm - D: 235mm
Battery Case: W:470mm - H: 220mm - D: 200mm
Weight Main Unit: 21.2 Kg
Battery Case: 5.15 Kg 

X